Contact us for a quote
| brand | |
|---|---|
| Model Number | |
| weight | 425kg |
| Type |
Power supply
380/420 V-50 Hz-3 ph (208/230 V-380/575 V-60 Hz-3 ph) Y-Δ PWS DOL
Horsepower
58 hp
Displacement
193 m3
Cooling capacity at ARI conditions, R407C
161,1 kW
Cooling capacity at EN12900 MT conditions, R404A
100,6 kW
Cooling capacity at ARI conditions, R22
164,6 kW
Refrigerant
R1234yf, R134a, R22, R404, R407C, R450A, R507, R513A
Suction pipe
2 5/8″
Discharge pipe
1 5/8″
Weight
425 kg
LRA (PWS)
425 A (50 Hz/380 V)
MCC
128 A
Other remarks
Crankcase heater 300W, Discharge check valve, Includes capacity regulator, Includes oil CPI 170, Oil level switch, Overtemperature Sensor for motor, Suction and discharge temperatures sensors, Suction filter
Sound level
59,7 dB
Accessories
Discharge service valve 2″, INT69 Protector, Mounting grommets (4 units), Suction service valve
Application
MHBP
Technology
Fixed speed
Maximum oil temperature
100 °C
Maximum discharge temperature
110 ºC
Maximum winding temperature
110 ºC
We will contact you within 24 hours, please pay attention to the email from sales@profixshop.com.