Contact us for a quote
| brand | |
|---|---|
| Model Number | |
| weight | 840kg |
| Type |
Power supply
380/420 V-50 Hz-3 ph (208/230 V-380/575 V-60 Hz-3 ph) Y-Δ PWS DOL
Horsepower
1,75 hp
Displacement
583 m3
Cooling capacity at ARI conditions, R407C
509,1 kW
Cooling capacity at EN12900 MT conditions, R404A
319,0 kW
Cooling capacity at ARI conditions, R22
535,8 kW
Refrigerant
R1234yf, R134a, R22, R404, R407C, R450A, R507, R513A
Suction pipe
4 1/8″
Discharge pipe
3 1/8″
Weight
840 kg
LRA (PWS)
1400 A (50 Hz/380 V)
MCC
377 A
Other remarks
Crankcase heater 300W, Discharge check valve, Includes capacity regulator, Includes oil CPI 170, Oil level switch, Overtemperature Sensor for motor, Suction and discharge temperatures sensors, Suction filter
Sound level
66,9 dB
Accessories
Discharge service valve 3″, INT69 Protector, Mounting grommets (4 units), Suction service valve
Application
MHBP
Technology
Fixed speed
Maximum oil temperature
100 °C
Maximum discharge temperature
110 ºC
Maximum winding temperature
110 ºC
We will contact you within 24 hours, please pay attention to the email from sales@profixshop.com.